Key Features
Output voltage 12, 24, 48Vdc, even in the absence of power supply
Output current 2.5A ÷ 25A, even in the absence of AC mains
Automated power sharing of available power between load and battery charging
Power boost, up to 3 times the rated current available. Ability to handle high current surges
"Main or back-up" and "battery failure/discharge" signaling relays with galvanically isolated output contacts
Fault signaling via relay contact, blink code, and Modbus RTU and TCP/IP protocols
Output power: 250W, 280W, 500W, 600W
DC-UPS and battery self-diagnosis: high voltage; sulfated battery; reverse connection; possible shorted element; short circuit protection
Accessories: battery temperature sensor, external display, PC and Modbus connection cables
Ultracompact design
Temperature operation range -40 ÷ 70°C
Products
All in one 12Vdc with Modbus RTU RS485
-
Input: Single-phase 115 – 277 Vac; 550W
Output Load: power supply 12 Vdc; 35 A
Output Battery: charging 12 Vdc; 35 A
Suited for the following battery types: Open Lead Acid, Sealed
Lead Acid, Lead Gel, Li-Ion and Ni-Cd, Li-Ion
Automatic diagnostic of battery status. Charging curve IUoU,
constant voltage and constant current Battery Life Test function
(Battery Care)
Switching technology, output voltage 10-14.4 Vdc
Three charging levels: Boost, Float and Recovery
Protected against short circuit and inverted polarity
Signal output (contact free) for discharged or damaged battery
Signal output (contact free) for mains or Back-UP
All in one 24Vdc with Modbus RTU RS485
-
Input: Single-phase 115 – 230 Vac (277 Vac operational)
Output Load: power supply 24 Vdc; 20A
Power boost: 25A (4 minutes)
Output Battery: charging 24 Vdc; 20A
Suited for the following battery types: Open Lead Acid,
Sealed Lead Acid, lead Gel and Ni-Cd, Ni-MH, Li-Ion
Automatic diagnostic of battery status.
Charging curve IUoU, constant voltage and constant
current Battery Life Test function (Battery Care)
Switching technology Four charging levels: Recovery,
Bulk, Absorption, Boost, and Float
Protected against short circuit and inverted Batt. polarity
Signal output (contact free) for discharged or damaged
battery
Signal output (contact free) for Mains or Back-UP
Modbus RTU for all parameter, Battery and System
All in one 48Vdc with Modbus RTU RS485
-
Input: Single-phase 115 – 277 Vac; 600W
Output Load: power supply 48 Vdc; 12.5 A
Output Battery: charging 48 Vdc; 12.5 A
Suited for the following battery types: Open Lead Acid,
Sealed Lead Acid, lead Gel and Ni-Cd, Ni-MH, Li-Ion
Automatic diagnostic of battery status.
Charging curve IUoU, constant voltage and constant
current Battery Life Test function (Battery Care)
Switching technology Four charging levels: Recovery,
Bulk, Absorption, Boost, and Float
Protected against short circuit and inverted Batt. polarity
Signal output (contact free) for discharged or damaged
battery
Signal output (contact free) for Mains or Back-UP
Modbus RTU for all parameter, Battery and System
Protection degree IP20 - DIN rail; Space saving
All in one 12-24Vdc with Modbus RTU RS485
-
Input: Single-phase 100 - 240 - 277 Vac
Output Selectable Load: 12 Vdc 15A; 24 Vdc 10A
Output Battery charging: 12 Vdc 15A; 24 Vdc 10A
Suited for the following battery types: Open Lead Acid,
Sealed Lead Acid, Lead Gel, Lead Crystal, Ni-Cd, Ni-MH, Li-Ion
Automatic diagnostic of battery status. Charging curve IUoU,
constant voltage and constant current Battery Life Test
function (Battery Care)
Four charging levels: Boost, Absorption, Float, Recovery
Protected against short circuit and inverted polarity
Signal output (contact free) for discharged or damaged
battery
Signal output (contact free) for mains or Back-UP
Modbus RTU for all parameter battery and system
Protection degree IP20
DIN rail; Space saving
-
▪ Input: Single-phase 100 – 240 - 277 Vac / 140 – 340 Vdc
▪ Output Selectable Load: 12 Vdc 10A; 24 Vdc 10A
▪ Two output: 1 Continuous, 1 Dynamic: On/Off by Modbus
▪ Output Battery charging: 12 Vdc 10A; 24 Vdc 10A
▪ Two load outputs: one static; one dynamic for: On/Off, Dimmer
(LED, DC brush motors), Fuse Breaker, PC shutdown and more
▪ Modbus RTU for Monitoring, Configuration, History and Alarms.
▪ ADELBus: integrated monitoring and control of ADELSystem
devices such as MRF10x e-Fuses and display.
▪ Suitable for the following battery types: Open Lead Acid, Sealed
Lead Acid (AGM/VRLA), lead Gel, Li-Ion and NiCd/NiMH
▪ Battery Care: Automatic diagnostic of battery state-of-charge
(SoC) and state-of-health (SoH).
▪ Charging curve IUoU, constant voltage and constant current.
▪ Five charging levels: Recovery, Boost, Absorption, Float (Forced
trickle / Forced float / Auto float-trickle), and Refresh
▪ Battery purification for battery reinvigoration
▪ Protected against short circuit and reversed polarity
▪ Signal output (contact free) for: discharged or damaged battery,
Mains or Back-up, rectifier failure
▪ Protection degree IP20 - DIN rail; Space saving